Bossier City, LA Fire Regulations: Propane Storage (2026)

Significant Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Governing sections
Bossier City Code §§ 50-34 to 50-36
Permit threshold
any LP-gas installation, any size (§ 50-36(e))
Above-ground tank approval
required over 100 gallons (§ 50-34)
Underground tanks
prohibited (Section 1701.4.4(b))
Bulk storage
restricted to fire limits (§ 50-35)
Appeal
to city council within 30 days (§ 50-38)

Summary

Bossier City requires a bureau of fire prevention permit for any above-ground LP-gas storage tank over 100 gallons and for every liquefied-petroleum-gas installation regardless of size. Secs. 50-34 through 50-36 tie tank siting to N.F.P.A. 58 and the city's fire limits, and flatly ban underground LP-gas containers anywhere in the city.

(a)Within the city limits as established by section 18-34 the storage of above ground tanks will be allowed in all residential areas as long as the liquefied petroleum gas commission, N.F.P.A. 58 and all adopted codes are followed. The bureau of fire prevention must permit and approve the installation of all above ground storage tanks over 100 gallons. ... The limits in which bulk storage of liquefied petroleum gas is restricted, are hereby established as the fire limits as established by section 18-34. ... Section 1701.4.2 Location of containers. a.Within the city limits as established by section 18-34 the location and size of all above ground storage tanks will meet N.F.P.A. 58. ... Section 1701.4.4 b. The installation of underground containers is prohibited.

Full Breakdown

Chapter 50's Fire Prevention Code article, adopted under Sec. 50-31, incorporates the Standard Fire Prevention Code and NFPA 101 by reference, then amends specific sections to fit Bossier City. Sec. 50-34 allows above-ground flammable-liquid storage tanks, including LP-gas tanks, in residential areas only if the installation follows the Liquefied Petroleum Gas Commission, NFPA 58 and the city's adopted codes, and it requires the bureau of fire prevention to permit and approve any above-ground storage tank over 100 gallons before installation. Sec. 50-35 goes further for bulk LP-gas storage specifically, restricting it to the fire limits established under Sec.

18-34, the same limits that already control where explosives, blasting agents and new bulk plants for flammable or combustible liquids can locate. Sec. 50-36 layers in a rewritten Section 1701 from the adopted fire code: a permit is required for every LP-gas installation irrespective of size of containers or type of occupancy, the bureau of fire prevention can demand plans before installation near adjoining occupancies or unusual conditions, and Section 1701.4.2 as amended requires that the location and size of every above-ground storage tank meet NFPA 58.

The same amendment package, Section 1701.4.4(b), flatly prohibits installing underground LP-gas containers anywhere within city limits, with no exceptions listed. A property owner who disagrees with the fire chief's permit decision can appeal to the city council within 30 days under Sec. 50-38. Because Chapter 50 doesn't set its own fine for these sections, a violation defaults to Sec. 1-9's general Code penalty: up to $500.00 in fines, up to 60 days in jail, or both, with each day of continued violation a separate offense.

Violations & Fines

Installing an LP-gas system without the required bureau of fire prevention permit, exceeding the 100-gallon above-ground threshold without approval, or installing an underground LP-gas container violates Secs. 50-34 through 50-36. With no fine written into Chapter 50 for these sections, Sec. 1-9's general penalty controls: up to $500.00, up to 60 days in jail, or both, and each day of noncompliance counts separately.

Frequently Asked Questions

Do I need a permit to install a propane tank in Bossier City?
Yes. Sec. 50-36(e) requires a permit for every liquefied-petroleum-gas installation regardless of container size or occupancy type, and Sec. 50-34 additionally requires bureau of fire prevention approval for any above-ground tank over 100 gallons before it's installed on the property.
Can I bury a propane tank underground in Bossier City?
No. Section 1701.4.4(b), as adopted by Sec. 50-36(i), prohibits installing underground LP-gas containers anywhere in the city; every installation has to be above ground and sized to meet NFPA 58 under Section 1701.4.2, with the bureau of fire prevention approving the plans.
Where can bulk LP-gas storage locate in Bossier City?
Sec. 50-35 restricts bulk liquefied-petroleum-gas storage to the fire limits established under Sec. 18-34, the same zone that already controls where explosives, blasting agents and new bulk plants for flammable or combustible liquids are allowed to locate in the city.

Sources & Official References

Other rules in Bossier City

All Bossier City rules

Compare Bossier City to another location·View the Louisiana fire regulations overview