Eden Prairie, MN Fire Regulations: Propane Storage (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Permit threshold
Fire Dept. permit needed at 500 gallons water capacity
Protection threshold
Burial, mounding or water system required at 2,000 gallons
Enforcing official
Fire Chief as Fire Code Official
Appeal path
Board of Adjustments and Appeals within 30 days

Summary

In the City of Eden Prairie, Fire Code amendment Section 9.05.G adds new MSFC Section 6103 for liquefied petroleum gas containers. An installer needs a Fire Department permit and plan approval before installing a single LP-gas container, or interconnected containers, totaling 500 gallons of water capacity or more. Containers at or above 2,000 gallons, single or interconnected, must also be buried, mounded, or protected by an approved water-application system or another Fire Code Official-approved method.

G.Amendment to Chapter 61 - LIQUEFIED PETROLEUM GASES.1.Chapter 61 is amended to add the following new section 6103: 6103.1 Permit. An installer must obtain a permit and plan approval from the Fire Department prior to installation of a single container or an aggregate of interconnected containers of 500 or more gallons water capacity. 6103.2 Protection. All single container installations with a total water storage capacity of 2,000 gallons or greater, and interconnected containers in the aggregate greater than 2,000 gallons, shall be protected by one or more of the following methods: 1.Buried in an approved manner.2.Mounded in an approved manner.3.By a system for application of water approved by the Fire Code Official.4.By other means approved by the Fire Code Official.

Full Breakdown

Eden Prairie adopts the Minnesota State Fire Code as its Fire Code under Section 9.05, Subd. 1, with the Fire Chief serving as the Fire Code Official who enforces it through the department of fire prevention under Subd. 2. Subd. 3.G adds a new Section 6103 to Chapter 61 of the MSFC dealing specifically with liquefied petroleum gases. Section 6103.1 requires an installer to get a Fire Department permit and plan approval before putting in a single LP-gas container, or an interconnected group of containers, that reaches 500 gallons of water capacity or more; smaller residential-sized tanks below that threshold fall outside the permit requirement.

Section 6103.2 adds a physical-protection rule once a single container, or interconnected containers in the aggregate, reach 2,000 gallons: the installation must be buried in an approved manner, mounded in an approved manner, protected by a Fire Code Official-approved water-application system, or protected by another method the Fire Code Official approves. The general permit provisions in Subd. 6 apply on top of these specific rules: applications go to the Fire Department on City forms, the Fire Code Official can deny a permit that would violate any law or endanger public health, safety or welfare, permits carry conditions and fees set by the City, and a permit is subject to revocation for a compliance failure. An installer who disagrees with a permit denial can appeal to the Board of Adjustments and Appeals within 30 days under Subd. 9.

Violations & Fines

Installing a 500-gallon-or-larger LP-gas container, or an interconnected system reaching that size, in Eden Prairie without the Section 6103.1 Fire Department permit and plan approval is a Fire Code violation enforced by the Fire Code Official. Skipping the burial, mounding or water-protection system required by Section 6103.2 once a container or interconnected system reaches 2,000 gallons is a separate violation, and the Fire Code Official can revoke an existing permit under Subd. 6 for noncompliance.

Frequently Asked Questions

Do I need a permit for a propane tank at my Eden Prairie home?
Only once the tank, or an interconnected group of tanks, reaches 500 gallons of water capacity or more. Section 6103.1 of the City's Fire Code amendment requires an installer to get a Fire Department permit and plan approval before installing a container that size or larger; smaller residential tanks are not covered by this specific permit rule.
What extra protection does a large propane tank need in Eden Prairie?
Once a single tank, or interconnected tanks together, reach 2,000 gallons of water capacity, Section 6103.2 requires the installation to be buried, mounded, protected by a Fire Code Official-approved water-application system, or protected by another method the Fire Code Official signs off on.
Who enforces LP-gas installation rules in Eden Prairie?
The Fire Chief acts as the City's Fire Code Official under Section 9.05, Subd. 2, and the department of fire prevention issues and enforces the Section 6103 permit and protection requirements for liquefied petroleum gas containers. A denied permit can be appealed to the Board of Adjustments and Appeals within 30 days under Subd. 9.

Sources & Official References

Other rules in Eden Prairie

All Eden Prairie rules

Compare Eden Prairie to another location·View the Minnesota fire regulations overview

Get notified when Propane Storage in Eden Prairie, MN changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Propane Storage in Nearby Cities

How other cities in Hennepin County handle propane storage.

Minneapolis, MN
Some Restrictions