Roseville, MN Fire Regulations: Smoke Detectors (2026)
Key Facts
- Governing section
- § 906.09(d)(8), with section 907 of the state fire code
- Required locations (R-2, R-3, R-4, I-1)
- Outside sleeping areas, in sleeping rooms, on each story
- Replacement age
- Not more than ten years from date of manufacture
- Distance from bathroom door
- Not less than three feet horizontally
- Photoelectric alarm near cooking appliance
- Not less than six feet horizontally
- Responsible party
- Owner of the premises
Summary
Roseville's property maintenance chapter requires single-station smoke alarms in existing Group I-1 and R occupancies and ties installation and interconnection to section 907 of the state fire code. Groups R-2, R-3, R-4 and I-1 need alarms outside each sleeping area, in each sleeping room and on each story, and alarms in one- and two-family dwellings must be replaced within ten years.
(8) Smoke alarms. Single or multiple-station smoke alarms shall be installed and maintained in existing Group I-1 and R occupancies in accordance with section 907 of the state fire code and the following: ... d. Groups R-2, R-3, R-4 and I-1. Single or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bed rooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. ... (12) Testing and maintenance. Single and multiple-station smoke alarms shall be tested and maintained in accordance with the manufacturer's instructions. Smoke alarms that do not function shall be replaced. Smoke alarms installed in one and two-family dwellings shall be replaced not more than ten years from the date of manufacture marked on the unit or shall be replaced if the date of manufacture cannot be determined.
Official source re-checked November 3, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 2).
Full Breakdown
Section 906.09(d)(8) governs smoke alarms in existing buildings. It requires single or multiple-station alarms to be installed and maintained in existing Group I-1 and R occupancies in accordance with section 907 of the state fire code, which the city adopted by reference in § 902.01. Under § 906.09(a)(2), the owner of the premises must provide and maintain the safety equipment, and no one can occupy or permit another person to occupy premises that fail the section.
Locations depend on the occupancy group. In Groups R-2, R-3, R-4 and I-1, alarms go on the ceiling or wall outside each separate sleeping area near the bedrooms, in each room used for sleeping, and in each story of a dwelling unit including basements but not crawl spaces and uninhabitable attics. Group R-1 adds alarms in every room in the egress path from the sleeping area to the door.
Placement limits follow. Ionization alarms stay at least 20 feet horizontally from a permanently installed cooking appliance, or ten feet if they have an alarm-silencing switch, and photoelectric alarms stay at least six feet away. Alarms also sit not less than three feet horizontally from the door of a bathroom with a tub or shower. Each limit gives way if it would block a required location.
Power and wiring are covered in (d)(9) and (d)(10). Single-station alarms take primary power from building wiring with a battery backup, except that battery-only alarms are permitted in buildings where construction is not taking place. Where more than one alarm is required in a unit, they must be interconnected, and listed wireless alarms satisfy that if all sound together. Paragraph (d)(12) requires testing per the manufacturer's instructions, replacement of any alarm that does not function, and replacement of alarms in one and two-family dwellings not more than ten years from the manufacture date marked on the unit.
Violations & Fines
A violation of Chapter 906 is unlawful under § 906.03(g)(1). The code official serves a written notice that includes a correction order allowing a reasonable time to comply. Failing to comply with that notice is a misdemeanor or civil infraction as the city determines, and the violation is a strict liability offense. Each day a violation continues after due notice counts as a separate offense. Costs the city incurs to correct the problem become a lien on the real estate.
Frequently Asked Questions
Where do smoke alarms have to go in a Roseville apartment or house?
How old can a smoke alarm be in a Roseville single-family home?
Do Roseville smoke alarms have to be wired together?
Who has to keep the smoke alarms working in a Roseville rental?
Sources & Official References