Skokie, IL Building Safety: Electrical Permits (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Code adopted
2020 National Electrical Code (NFPA 70)
New service
Must be underground unless infeasible
Sub-panels
Barred on single-phase 100-amp service
Raceway
Non-metallic raceway/cable prohibited
Grounding
Copper wire required for grounds/bonding
Enforcing official
Village Manager or designee

Summary

Skokie adopts the 2020 National Electrical Code, NFPA 70, by reference under Village Code Section 22-91, governing every electrical installation in the village, Cook County, Illinois. Section 22-93 layers on local amendments before an electrical permit is issued: underground service is required for new construction unless the Village Manager or designee finds it impractical, non-metallic raceway is generally banned, and sub-panels cannot be added to a single-phase 100-amp service.

Pursuant to authority granted by 65 ILCS 5/1-3-2, the Village hereby adopts by reference the National Electrical Code, 2020 Edition, and all regulations thereto, as published by the National Fire Protection Association, as the electrical code, excepting those provisions which are modified or deleted as provided in this article. ... Sub-panels will not be allowed to be added to single phase 100 Amp services.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 205 | Zoning: Supplement 89).

Full Breakdown

Section 22-91 adopts the National Electrical Code, 2020 Edition, published by the National Fire Protection Association, as Skokie's electrical code under authority of 65 ILCS 5/1-3-2, with Section 22-92 giving any conflicting Village ordinance priority over the model code. Section 22-93 amends the adopted NEC in specific, quotable ways that shape what an electrical permit application must show. New commercial, industrial and residential structures requiring electrical service must be served underground unless the Village Manager or designee determines underground service is not feasible. Copper wire is mandated for all ground conductors and bonding jumpers, and non-metallic raceway or cable is prohibited outright; electrical metallic tubing, rigid conduit or intermediate metal conduit must enclose branch circuit wiring, with flexible metal conduit allowed only in accessible locations up to 6 feet unless the Village grants special permission for a longer run.

Sub-panels may not be added to an existing single-phase 100-amp service, a restriction aimed at overloaded older Skokie housing stock. GFCI protection is waived for single-receptacle sump, ejector and lift-station pumps and for HVAC condensers with a properly sized equipment grounding conductor, and AFCI protection is not required on branch circuits feeding kitchen counter outlets, kitchen appliances, furnaces, motors and pumps that may arc in normal operation. Contractor registration and insurance requirements set elsewhere in Chapter 22 and permit fees under Chapter 46 apply to electrical work performed under the adopted code, and Section 22-1's general penalty provisions and Section 22-2's notice-and-hearing procedure govern enforcement.

Violations & Fines

Electrical work performed without complying with the adopted National Electrical Code amendments in Section 22-93, such as installing prohibited non-metallic raceway or adding a sub-panel to a single-phase 100-amp service, is a violation of Chapter 22 under Section 22-1 and draws the general penalties fixed in Sections 1-6 and 1-7. A written notice under Section 22-2 must precede any penalty, giving the violator the right to a court appearance or administrative hearing.

Frequently Asked Questions

What electrical code does Skokie enforce?
The Village adopted the 2020 National Electrical Code, NFPA 70, by reference in Village Code Section 22-91, and it governs every electrical installation in Skokie, Cook County, Illinois. Section 22-92 makes any conflicting Village ordinance control over the NEC itself, and Section 22-93 layers on Skokie-specific amendments that any electrical permit application must satisfy.
Can I add a sub-panel to my Skokie home's electrical service?
Not if your home runs on a single-phase 100-amp service. Section 22-93(11)(c) flatly bars adding a sub-panel to that service size, a local amendment to the adopted National Electrical Code aimed at older Skokie housing stock with limited service capacity.
Does Skokie require underground electrical service for new construction?
Yes. Section 22-93 amends the adopted NEC so new commercial, industrial and residential structures needing electrical service must be served underground and protected against physical damage, unless the Village Manager or designee determines underground service cannot be provided.

Sources & Official References

Other rules in Skokie

All Skokie rules

Compare Skokie to another location·View the Illinois building safety overview

Get notified when Electrical Permits in Skokie, IL changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.

Electrical Permits in Nearby Cities

How other cities in Cook County handle electrical permits.

Chicago, IL
Some Restrictions
Tinley Park, IL
Some Restrictions
Arlington Heights, IL
Some Restrictions
Evanston, IL
Some Restrictions
Schaumburg, IL
Some Restrictions
Oak Lawn, IL
Some Restrictions
Oak Park, IL
Some Restrictions