Wylie, TX Building Safety: Elevator Maintenance (2026)
Key Facts
- Enforcing agency
- Wylie Building Inspections Division
- Storage in elevator machine rooms
- Prohibited citywide
- Required signage
- "No Storage Allowed" at each entry
- Sprinklers in hoistways/machinery spaces
- Prohibited by local amendment
- Adopting ordinances
- Ord. No. 2017-32; amended Ord. No. 2022-12
- Maximum fine (fire/safety violation)
- $2,000.00 per day
Summary
In the City of Wylie, Texas, elevator machine rooms, control rooms and machinery spaces must stay clear of stored materials under the city's local amendments to the International Building Code. Sec. 22-42 bars automatic sprinklers inside elevator hoistways and machinery spaces, requires an approved method to keep sprinkler water outside those spaces from reaching the hoistway enclosure, and orders posted signage at every machine room entry.
3005.5.1.1.1 Prohibited locations. Automatic sprinklers shall not be installed in machine rooms, elevator machinery spaces, control rooms, control spaces and elevator hoistways. ... 3005.5.1. ... 2 Water protection. An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the elevator lobby shall be provided. ... 3005. ... 8 Storage. Storage shall not be allowed within the elevator machine room, control room, machinery spaces and or control spaces. Provide approved signage at each entry to the above listed locations stating: "No Storage Allowed.
Full Breakdown
Wylie's Building Inspections Division enforces elevator fire protection through Sec. 22-42, Amendments to the International Building Code, adopted by Ordinance No. 2017-32 on December 12, 2017 and revised by Ordinance No. 2022-12 on February 8, 2022. The amendment adds Section 3005.5.1 to the 2021 IBC, prohibiting automatic sprinklers inside elevator machine rooms, machinery spaces, control rooms, control spaces and hoistways, while requiring the building's fire alarm system to monitor the sprinkler control valve and water-flow devices on every floor. A separate water-protection clause requires an approved method to keep sprinkler water from outside the elevator lobby from infiltrating the hoistway enclosure, and the amendment eliminates the shunt-trip elevator shutdown requirement for firefighter and passenger safety.
New Section 3005.8 bars any storage in the elevator machine room, control room or machinery spaces and requires posted signage reading 'No Storage Allowed' at each entry. Work touching these systems needs a building permit under Sec. 22-4, and the Construction Code Board created under Sec. 22-21 hears appeals from the building official's decisions on these amendments. Because fire and life-safety code violations fall under the city's general penalty section, Sec. 1-13, a violation involving these elevator fire-protection or storage rules can draw a fine of up to $2,000.00 per day, with each day of noncompliance charged as a separate offense.
Violations & Fines
Storing materials in an elevator machine room, installing a barred sprinkler inside a machinery space or hoistway, or removing required water-protection or signage without correcting it is a Code violation citable by the building official under Sec. 22-3. Because it falls within the fire and safety category of Sec. 1-13, the general penalty section, each offense can be fined up to $2,000.00, and each continuing day of the violation counts as a separate offense.
Frequently Asked Questions
Can a Wylie building owner store supplies in an elevator machine room?
Are automatic sprinklers required inside a Wylie elevator hoistway?
Who enforces Wylie's elevator machine room fire rules?
What is the penalty for violating Wylie's elevator fire-protection amendments?
Sources & Official References
Other rules in Wylie
Texas rules heatmap·Compare Wylie to another location·View the Texas building safety overview
See something wrong?
Help us keep this page accurate. If you notice an error or outdated information, let us know.
Elevator Maintenance in Nearby Cities
How other cities in Collin County handle elevator maintenance.