Skip to main content
CityRuleLookup

Boca Raton, FL Building Safety: Carbon Monoxide Detectors (2026)

Some Restrictions
Compiled from the official code textEditor Martyn O'NeillLast verified September 2026

Key Facts

Governing section
Sec. 7-60(6)
Applies to
new buildings, new parking structures
Supervisory signal threshold
99 ppm
Evacuation alarm threshold
199 ppm
Standards referenced
NFPA 720, NFPA 72, NFPA 88A
Existing garages
add CO detection only on level 2/3 alteration

Summary

New buildings and new parking structures in Boca Raton must install carbon monoxide detection systems under Section 7-60(6) of the fire code. The devices must send a supervisory signal at 99 parts per million and trigger a full building evacuation alarm once CO exceeds 199 parts per million.

(6)Carbon monoxide detection systems shall be installed in new buildings as required by the FFPC, NFPA 720, and NFPA 72. Carbon monoxide detection systems shall be installed in new parking structures as required in NFPA 88A. Such installed carbon monoxide detection devices shall be programmed to provide a supervisory signal to the fire alarm panel and any area attended by security or staff at a level of 99 parts per million. Further, such carbon monoxide detection devices that detect a carbon monoxide level that exceeds 199 parts per million shall be programmed to send an alarm signal to the fire alarm panel activating notification devices alerting all occupants of the building to evacuate the building. Existing parking structures will be required to comply with this Code if a level 2 or level 3 alteration is conducted as defined by the Florida Building Code.

View official code

Official source re-checked September 7, 2026: no newer edition of the code had been published (publisher’s edition: Code of Ordinances: Supplement 72 Update 1).

Full Breakdown

Section 7-60(6) of the Boca Raton Code of Ordinances requires carbon monoxide detection systems in new buildings, following the standards in the Florida Fire Prevention Code, NFPA 720, and NFPA 72, and in new parking structures under NFPA 88A. The ordinance sets two distinct alarm thresholds rather than a single trigger point. At 99 parts per million, the detector must send a supervisory signal to the building's fire alarm panel and to any area staffed by security or building personnel, alerting staff to a developing problem without yet sounding a full evacuation alarm.

Once carbon monoxide reaches 199 parts per million, the same detection devices must be programmed to send a full alarm signal to the fire alarm panel, activating the building's notification devices so every occupant is alerted to evacuate. The requirement is prospective for parking structures already built: an existing parking structure only has to add carbon monoxide detection if it undergoes a level 2 or level 3 alteration as defined by the Florida Building Code, meaning older garages are not automatically required to retrofit detectors absent a qualifying renovation.

The detection requirement sits inside the same section that governs fire alarm and automatic extinguishing systems generally, so a CO detection system in a covered garage or mechanical room has to tie into the building's existing NRTL-monitored fire alarm panel rather than operate as a stand-alone device.

Violations & Fines

Failing to install carbon monoxide detection in a new building or new parking structure, or failing to program the two-tier 99 ppm supervisory and 199 ppm evacuation alarm thresholds, is enforceable as a Chapter 7 violation under Sections 7-4 and 7-5, carrying the same penalty as any other fire alarm system violation under the Florida Fire Prevention Code.

Frequently Asked Questions

Are carbon monoxide detectors required in new buildings in Boca Raton?
Yes. Section 7-60(6) requires carbon monoxide detection systems in new buildings under the Florida Fire Prevention Code, NFPA 720, and NFPA 72, and in new parking structures under NFPA 88A, tied into the building's fire alarm panel.
At what carbon monoxide level does the alarm actually evacuate the building?
At 199 parts per million. Below that, at 99 parts per million, the system only sends a supervisory signal to the fire alarm panel and staffed areas; once the level exceeds 199 ppm, it must trigger a full alarm activating notification devices to evacuate everyone.
Does an older Boca Raton parking garage need to add CO detectors?
Only if it undergoes a level 2 or level 3 alteration as defined by the Florida Building Code. Section 7-60(6) does not require existing parking structures to retrofit carbon monoxide detection absent that kind of qualifying renovation.

Sources & Official References

Other rules in Boca Raton

All Boca Raton rules

Florida rules heatmap·Compare Boca Raton to another location·View the Florida building safety overview

Get notified when Carbon Monoxide Detectors in Boca Raton, FL changes

We'll email you the moment we detect a change in the code. No spam, unsubscribe anytime.

We'll never sell or share your email. One-click unsubscribe in every email.

See something wrong?

Help us keep this page accurate. If you notice an error or outdated information, let us know.